Common Mistakes When an Aspirated Smoke Detection System is Set Up

Common Mistakes When an Aspirated Smoke Detection System is Set Up Featured Image

By installing an aspirated smoke detection system, you will ensure the safety of your workplace. It will assist you in the early detection of smoke. The system is reliable, and it has excellent sensitivity. It is essential to note that if the installation of the system is not done correctly, the outcome may be devastating. It may cause the death of people, and the property may be destroyed beyond repair, amounting to millions of pounds. You can find the right company to install the system by knowing the common mistakes to avoid.

Installation and Design Mistakes

Inadequate Network and Pipe Design

The heart of the Aspirated Smoke Detection System is the network of pipes. A poor system is a result of a poor network. Not using modeling software for designs like a pro is one of the common mistakes that should be avoided in the pipe network of the system. In order to execute your designs, you should use PipeIQ or modeling software ASPIRE. This will help you maintain the equilibrium in your sampling holes. The sampling holes will not let too much or too little air enter, thereby ensuring the robust protection of your building.

Incorrect Pipe Material Type

The performance of the aspirated Smoke Detection System also depends on the type of pipe material that is being used. The wrong type of material for the CPVC pipes in the plenum space is another major error in the pipe network. This may cause the rate at which the air travels to be reduced. The air will, therefore, take a longer time to move to the detector from the sampling hole. Time is of the essence during a fire.

Incorrect Placement of the Sampling Holes

Placing sampling holes in regions with high airflow is the biggest error. In front of HVAC diffusers, this frequently occurs. This may cause false alarms and interfere with business operations. The aspirated smoke detection system is effective. However, it should not be placed far from areas that could catch fire. Determine high-risk areas and place sampling locations at appropriate separations from them.

Disregarding Environmental Elements

Condensation may be a significant issue for a company that has cold storage spaces. The system may fail as a result of water clogging the pipes. Use special techniques to prevent this. They prevent condensation from getting to the sensor.

Inaccurate Sensitivity Configuration

Not every region is the same. Using the same sensitivity settings for a clean computer room and a dusty warehouse is a common error. False alarms will happen if the sensitivity is too high in a dusty area. However, smoke may not be detected in time if it is too low in a crucial area.

Errors in Maintenance and Operations

Neglect of Filter Maintenance

The installation might have been done perfectly, but that is just the beginning. Just like any other smoke detector, these systems need maintenance. One of the common errors is neglecting filter maintenance. This is because when the filter gets clogged, it forces the fans to work harder, causing them to fail prematurely.

Neglect of Cleaning of Pipes

The pipes might also be clogged, especially when dust and insects accumulate. This might cause problems, especially when it clogs the sampling holes and affects airflow within the system. It is, therefore, important to clean the pipes using a vacuum cleaner or compressed air.

Neglect of Using Correct Testing Methods

There are some service providers who may use a lot of spray for the testing. This is another mistake. This spray may clog the sampling holes within the system. This clog may affect the sensors within the system.

Secure Your Facility with Controlled Ltd

If you want to install an aspirated smoke detection system, use these points when interviewing a provider. Ask about pipe modeling or water traps. This tests their system knowledge. A true expert will explain their methods. In contrast, a less experienced provider may have trouble giving clear answers.

If you want to have a trained team for design, installation, and maintenance, Controlled Ltd is your best choice. We deliver high-performance fire safety systems designed for your business. Take a look at our aspirated smoke detection systems now.

See More Blog Articles

Contact us

Let's Connect for Your Security Needs

Contact Controlled Ltd for expert security solutions tailored to your industry.

Your benefits:

What happens next?

1

We Schedule a call at your convenience 

2

We do a discovery and consulting meeting 

3

We prepare a proposal 

Schedule a Free Consultation